NZ Transformer Fault Current Calculator
Use this free tool to estimate prospective fault currents at the LV terminals of any distribution transformer — for switchboard fault rating, protection coordination, and AS/NZS 3000 compliance.
Use this free tool to estimate prospective fault currents at the LV terminals of any distribution transformer — for switchboard fault rating, protection coordination, and AS/NZS 3000 compliance.
| Parameter | Formula | Description |
|---|---|---|
| Full-load current | Ifl = kVA × 1000 / (√3 × V) | Transformer rated full-load current (A) |
| Sequence impedances | Z1 = Z2 = Z0 = Z% / 100 | For Dyn transformer: Z0 = Z1 (delta primary confines zero-sequence to LV winding) |
| 3-phase fault | I3φ = Ifl / Z1 | Symmetrical three-phase prospective fault current |
| Phase-to-phase | Ipp = I3φ × √3 / 2 | Line-to-line fault ≈ 86.6% of 3-phase value |
| Phase-to-earth | Ipe = 3Vph / (Z1+Z2+Z0) = I3φ | With Z0=Z1, symmetrical components give Ipe = I3φ at LV terminals |
| Phase-to-neutral | IpN = Ipe | MEN system: neutral bonded to earth at transformer — fault path is identical |
| Parameter | Formula | Description |
|---|---|---|
| Full-load current | Ifl = kVA × 1000 / V | Rated secondary full-load current (A) |
| Series impedance | Z1 = Z% / 100 | Transformer leakage impedance (per-unit) |
| Bolted fault current | Isc = Ifl / Z1 | Prospective short-circuit current at LV terminals |
| Phase-to-earth | Ipe = Isc | MEN system: earth fault path through transformer winding impedance only at LV terminals |
| Phase-to-neutral | IpN = Isc | MEN system: neutral bonded to earth at transformer — fault path is identical |
| Sequence | Impedance | Basis |
|---|---|---|
| Positive sequence (Z1) | = Z% / 100 | Transformer nameplate impedance |
| Negative sequence (Z2) | = Z1 | Assumed equal to positive sequence |
| Zero sequence (Z0) | = Z1 | Dyn transformer — delta primary blocks zero-sequence from HV network; zero-sequence current circulates within the delta winding, so Z0 = transformer leakage impedance |
| Source impedance | = 0 | Infinite bus (conservative worst-case — maximises fault current) |
| Cable impedance | = 0 | Fault assumed at transformer LV terminals; add cable Z for downstream points |
| Neutral/earth path | = 0 | MEN bond at transformer — neutral and earth at same potential at source |