Clive Wilson / fault current calculator

Transformer fault current.
Start with the nameplate.

Use the CWS calculator for a preliminary transformer-terminal estimate. Enter the transformer rating, secondary voltage and impedance, then review the assumptions alongside the result.

CWS switchboard manufacturing in Invercargill
Before using the result

Keep the project conditions in view.

This tool supports an early specification discussion. It does not establish the rating or compliance of a completed switchboard. Confirm the source data, installation conditions and required verification with the responsible project designer.

Transformer Nameplate Data
Transformer rated output (kVA)
Enter a valid kVA > 0
LV line-to-line voltage (V)
Enter a valid voltage > 0
Transformer nameplate impedance (%)
Enter impedance between 0.1% and 20%

Calculation Method / 3-Phase (Dyn)

On smaller screens, scroll across the table to see every column.

ParameterFormulaDescription
Full-load currentIfl = kVA × 1000 / (√3 × V)Transformer rated full-load current (A)
Sequence impedancesZ1 = Z2 = Z0 = Z% / 100Assumed Z0 = Z1 for this simplified model; confirm the actual transformer zero-sequence impedance
3-phase faultI3φ = Ifl / Z1Symmetrical three-phase prospective fault current
Phase-to-phaseIpp = I3φ × √3 / 2Line-to-line fault ≈ 86.6% of 3-phase value
Phase-to-earthIpe = 3Vph / (Z1+Z2+Z0) = I3φWith Z0=Z1, symmetrical components give Ipe = I3φ at LV terminals
Phase-to-neutralIpN = IpeModel assumes zero additional neutral/earth return impedance at transformer terminals; verify actual paths
Sequence Impedance Assumptions (MEN / Dyn Transformer)

On smaller screens, scroll across the table to see every column.

SequenceImpedanceBasis
Positive sequence (Z1)= Z% / 100Transformer nameplate impedance
Negative sequence (Z2)= Z1Assumed equal to positive sequence
Zero sequence (Z0)= Z1Simplified assumption only; vector group alone does not establish the actual zero-sequence impedance. Confirm transformer data.
Source impedance= 0Infinite upstream source for this single-transformer model; not a guaranteed installation maximum
Cable impedance= 0Fault assumed at transformer LV terminals; add cable Z for downstream points
Neutral/earth path= 0MEN bond at transformer / neutral and earth at same potential at source
Engineering guidance: This calculator provides a simplified estimate at the LV terminals of one transformer. It assumes an infinite upstream source, zero cable impedance and simplified sequence modelling (Z0 = Z1 for the three-phase option). It does not include motor or other-source contributions, voltage factors, transformer impedance tolerances, parallel sources or the actual neutral/earth-return arrangement. Results are not guaranteed upper bounds. Earth and neutral results are model assumptions, not a verified earth-fault study.

Confirm the transformer data and installation conditions with the responsible electrical engineer before selecting equipment or protection. See our switchboard fault-rating guide and Schneider Electric’s transformer-terminal calculation guide.
Move from estimate to specification

Bring the inputs to CWS.

Send the single-line diagram, source information, load schedule and site conditions with your enquiry. Simotrol is our primary platform for main switchboards and MCCs, with the assembly configured around the project requirements.

Main switchboards Motor control centres
Contact CWS

Talk through your project.

Send your drawings, site requirements and project programme to our Invercargill team.

Printable quote checklist (PDF)Email your checklist, drawings and schedules to estimating@clivewilson.co.nz. Leave unknown items blank.

Contact our team