A 250 A circuit breaker.
The mains supply lands on a 250 A moulded case circuit breaker with an electronic trip unit and a rotary handle.
A 200 A main switchboard built by CWS for a water pump station, with mains and generator incomers and a 250 A automatic transfer switch between them.
A water pump station cannot wait for the power to come back. When the mains supply fails, a standby generator has to take over the load, then hand it back when the mains returns.
This main switchboard does that changeover on its own. It takes both supplies, keeps them apart and transfers the station from one to the other automatically.
CWS built the switchboard. The generator, its fuel system and its commissioning were by others.
The mains supply lands on a 250 A moulded case circuit breaker with an electronic trip unit and a rotary handle.
The generator supply has its own matching 250 A circuit breaker, so either source can be isolated and protected on its own.
A 250 A four-pole motorised transfer switch with its own controller changes the station over between the two supplies.
The switchboard is built to Form 4 internal separation in an IP54 enclosure, with a documented rating of 200 A and 25 kA for 1 second.
A transfer switch of this type has three positions: mains, off and generator. It cannot connect both supplies to the load at once.
The controller watches the supplies and drives the switch. A handle is provided so the switch can also be worked by hand.
Explore generator changeover panelsAn automatic transfer switch suits sites that must restore supply with nobody there, such as pump stations. Where an operator connects a generator by hand, key-interlocked switches are simpler.
The ratings on this page belong to this project. A new switchboard is rated for its own supply and its own site.
Explore water and wastewater switchboardsSend the supply details, the generator size and how the changeover should work.