Generator changeover and interlock panels

We build the changeover between your mains supply and a generator: automatic transfer switches, key-interlocked incomers, manual changeover switches and generator connection points. The generator is supplied by others. CWS builds the switching and the interlocking that keeps the two supplies apart.

Key-interlocked mains and generator isolators with busbars to the load connections in a changeover panel

Automatic transfer for a pump station

A pump station main switchboard with a mains incomer, a generator incomer and a 250 A automatic transfer switch. On loss of mains the transfer switch moves the load to the generator supply.

Pump station changeover ratings
Ratings of this project. They do not transfer to another board.
ItemAs built
Transfer switch250 A, four pole, automatic
Incomers250 A moulded case circuit breakers, mains and generator
Board rated current200 A
Short-time withstand25 kA for 1 second
Form of separationForm 4
Enclosure protectionIP54

Read the full project: Pump station switchboard with automatic transfer.

250 A motorised automatic transfer switch inside a pump station switchboard
The 250 A motorised transfer switch in the pump station switchboard.

Plan the changeover

Automatic, manual or key interlocked

The choice depends on how quickly the load must be restored, who is on site, and whether the generator is permanent or brought in when needed.

Changeover arrangements we have built
Ratings belong to each project and do not transfer to another board.
ArrangementHow it worksBuilt examples
Automatic transfer switch (ATS)Transfers the load to the generator supply under a controller when the mains is lost.80 A to 400 A, for pump stations, a supermarket, a medical centre and a cafe.
Key-interlocked incomersTwo incomers share one key, so only one can be closed at a time.100 A to 1,600 A, including 630 A isolators for an EV charging site and 1,600 A incomers for a coolstore.
Manual changeover switchOne switch selects mains, off or generator.A 125 A farm distribution board.
Generator connection pointAn inlet socket or connection panel where a mobile generator is plugged in or cabled.A 125 A inlet on a farm board, and stainless steel connection panels from 400 A to 800 A.

Supply and generator data

Send the single line diagram, the generator rating, its neutral and earthing arrangement, and the fault level from each source. The number of switched poles depends on that arrangement and is confirmed with the project designer.

Loads the generator must carry

Say which loads stay on when the generator is running. Where the generator cannot carry everything, essential and non-essential loads can be separated or shed.

Controls and signals

Agree the generator start signal, the transfer controller and what the site needs to see: which source is available, the switch position and any alarms.

Who supplies what

CWS supplies the switchboard, the changeover and the interlocking. The generator, its fuel system and its commissioning are by others.

Key-interlocked isolators for a 630 A site

A 630 A changeover panel for an EV charging site, in a 304 stainless steel enclosure rated IP55. A grid isolator and a generator isolator share one key, so only one can be closed. Short-time withstand 20 kA for 1 second, Form 1.

Read the full project: 630 A key-interlocked changeover panel.

Stainless steel generator changeover panel with doors open, showing two interlocked isolators
The stainless steel changeover panel with its doors open.

A labelled incomer for each source

Each supply has its own incomer, labelled for its source. Tell us what your operators need to see and do at the board when the supply changes.

For the rest of the board, see main switchboards.

Mains incomer and generator incomer circuit breakers, each labelled, inside a switchboard
Mains incomer and generator incomer, side by side.

Generator changeover questions

Do you supply the generator?

No. CWS supplies the switchboard, the changeover and the interlocking. The generator is supplied and commissioned by others.

What is the difference between an ATS and a manual changeover?

An automatic transfer switch changes source under a controller when the mains is lost. A manual changeover switch is operated by a person. Key-interlocked incomers are also manual: one key allows only one incomer to be closed.

Can a changeover be added to an existing switchboard?

Sometimes. It depends on the space, the busbar arrangement, the ratings and the records for the existing board. Send the drawings and photographs. Compare upgrade and replacement.

Can you provide a connection point for a mobile generator?

Yes. We have built generator inlet sockets on smaller boards and stainless steel generator connection panels from 400 A to 800 A.

What size changeovers have you built?

Automatic transfer switches from 80 A to 400 A, and key-interlocked incomers up to 1,600 A.

Discuss a generator changeover

Send the single line diagram, the generator details and the loads to be supported.