1. Audit the board
Start with the board as it stands. Send photographs, the nameplate, any drawings and the fault level if it is known. The audit sets the priorities for everything after it.
For switchboards already in service. We audit the board as it stands, record it as current drawings and a 3D model, and fit monitoring equipment so the board reports its own condition.
A structured review of an existing switchboard, on site. We check the board against six areas: a defined and supported design, protection matched to the circuits, correct fault duty, an enclosure and layout that can be used safely, clear identification and current records, and monitoring that serves a purpose.
You receive a written report: what was found, what matters most and the options for each item. It is a condition review to plan work from. It is not a certificate of compliance.
Start with the board as it stands. Send photographs, the nameplate, any drawings and the fault level if it is known. The audit sets the priorities for everything after it.
We survey the board and redraw it: single line diagram, schematics, layout and a 3D model of the assembly. A board with no drawings, or drawings that no longer match, gets a current record.
Sensors and a gateway are fitted during a planned shutdown. Wireless sensors need no signal wiring to each point, which suits boards that were never built for monitoring.
| What is measured | Equipment | Where it goes |
|---|---|---|
| Temperature of connections | Schneider PowerLogic TH110 wireless thermal sensors | Busbar joints, cable terminations and circuit breaker connections. |
| Temperature and humidity in the cubicle | Schneider PowerLogic CL110 wireless sensors | On a de-energised surface inside the enclosure. |
| Early signs of overheating insulation | Schneider PowerLogic HeatTag | In the cubicle air. It is an early warning device, not a fire protection device. |
| Power and energy | Power meters and circuit breaker metering | Incomers and selected feeders. |
| Collecting the readings | Schneider EcoStruxure Panel Server gateway | In the board, connected to your network. |
Readings and alarms go to the gateway, then to your SCADA, BMS or the manufacturer’s software. Who owns the network connection, the software and any subscription is agreed in the scope.
Where the audit finds obsolete breakers or a section at the end of its life, the same survey informs the next step: an ACB retrofit, a replacement section or a new board. Compare upgrade and replacement.
CWS builds full 3D models of switchboards and switchrooms. The model shows the board as built: sections, doors, devices and cable zones, to scale. Use it to plan modifications, brief contractors before a shutdown and check access without opening the board.
The model and drawings are a record of one particular board. Linking that record to live readings from the monitoring equipment is scoped project by project.
CWS has fitted EcoStruxure Panel Server gateways in distribution boards and motor control centres. On a new board, monitoring points are agreed at design stage so sensor positions, clearances and access are allowed for in the layout.
Six areas: the design and its supporting records, protection, fault duty, the enclosure and layout, identification and drawings, and monitoring. You receive a written report with the findings in priority order.
A digital record of one particular board: its single line diagram, schematics and a 3D model of the assembly as built. With monitoring fitted, readings from the board can be read against that record.
Often. Wireless sensors need no signal wiring to each point, but they do need safe access to the connections, so fitting is planned for a shutdown. The board is assessed first.
No single method does everything. Fixed sensors watch chosen connections continuously. A thermal survey looks across the board at one moment. Both belong in the maintenance plan.
To a gateway in the board, then to your SCADA, BMS or the manufacturer’s software. The network connection, software and any subscription are agreed in the scope.
Yes. We work on main switchboards, motor control centres and distribution boards built by others. Send the drawings and nameplate details you have.
Send the site location, board photographs, nameplate details and any drawings. Tell us what you want to know about the board.