Air circuit breaker retrofits for existing switchboards

We replace obsolete air circuit breakers (ACBs) in existing main switchboards and motor control centres. The board stays. The breaker, its copper connections, the door plate and the control wiring are renewed, and prepared in our Invercargill workshop before your shutdown.

New drawout air circuit breaker racked into its cradle inside an existing main switchboard cubicle

Copper and door plates made before the shutdown

An older cubicle rarely matches a new breaker. We measure the existing busbar connections and the door cut-out, then make copper adaptor bars and a door adaptor plate to suit the new cradle. The outage is then used for fitting and testing, not for working things out.

See the dairy plant retrofit work

Copper adaptor bars joining existing busbars to the cradle of a new air circuit breaker during a retrofit
Copper adaptor bars join the existing busbars to the cradle of the new breaker.

Plan an ACB retrofit

Existing board survey

Send the breaker nameplate, the board drawings and photographs of the cubicle with the door open. We confirm the cradle, busbar connections, door cut-out and control wiring before proposing a replacement.

Replacement breaker and protection

The replacement is chosen for the circuit and the fault level at the board, not on frame size alone. Recent retrofits have used Schneider Electric MasterPact MTZ and Terasaki air circuit breakers.

What changes in an ACB retrofit
Typical scope. Each retrofit is specific to the existing assembly.
PartWhat we checkWork carried out
Breaker and cradleRated current, breaking capacity and short-time withstand against the fault level at the board.New drawout breaker and cradle fitted in the existing cubicle.
Busbar connectionsPosition and size of the existing top and bottom connections.Copper adaptor bars made to join the existing busbars to the new cradle.
DoorCut-out and fixings left by the old breaker.New door adaptor plate around the new breaker.
Control wiringClosing, tripping, spring charging, interlocks and remote signals.Control wiring redrawn and connected to the new breaker.
Protection settingsExisting settings and the site’s protection study.Settings agreed with the site’s protection designer and recorded.

Shutdown plan

Tell us the outage window and what must stay live. Adaptor copper, door plates and wiring are made and checked beforehand so the shutdown covers installation and testing.

Testing and drawings

We agree the checks to be made before the board returns to service, and update the drawings to show the new breaker and its control wiring.

Breaker positions from 800 A to 3,200 A

CWS has replaced air circuit breakers in existing switchboards since the mid-2000s, in dairy plants, wood processing and heavy industry. Breaker positions have ranged from 800 A to 3,200 A, including incomers and bus ties.

An ACB retrofit is not the right answer for every ageing board. Where the assembly itself is no longer suitable, a new main switchboard is the better path.

Replacement air circuit breaker in its cradle with the cubicle door open and control terminals above
A replacement drawout breaker in its cradle, with the control terminals above.

ACB retrofit questions

Is an ACB retrofit always possible?

No. The existing assembly has to be assessed for condition, ratings, documentation, busbar arrangement and cable interfaces. Where those cannot be resolved, replacing the switchboard may be the better option. Compare upgrade and replacement.

Which air circuit breakers do you fit?

Recent retrofits have used Schneider Electric MasterPact MTZ and Terasaki air circuit breakers, replacing older Masterpact and Terasaki breakers. The replacement is selected for the circuit and the fault level at the board.

How long does the shutdown need to be?

It depends on the number of breakers, the access and the testing required. The copper, door plates and wiring are made beforehand so the outage covers installation and testing only. Tell us the window you have.

Do you retrofit switchboards built by other manufacturers?

Yes. We work on main switchboards and motor control centres built by others. Send the drawings, nameplate details and photographs you have.

What breaker ratings have you worked on?

Breaker positions from 800 A to 3,200 A, including incomers and bus ties.