Collect the inputs that affect the layout
Record the exact drive model, supply voltage, load duty, switching-frequency assumptions and manufacturer installation conditions. Identify the heat released inside the enclosure, any losses removed through a separate path and the equipment that operates at the same time.
Include other heat sources: line or output reactors, filters, power supplies, control equipment and the relevant switchgear and conductor losses. The thermal brief should also state ambient conditions, enclosure location, clearances and any altitude or derating requirements from the selected equipment.
Do not substitute motor kW for the drive’s heat loss or assume that every model at a given rating has the same dissipation. Rittal’s enclosure guidance begins with component heat losses and the environment in which the enclosure operates.
Provide the data before the general arrangement is final. Cooling hardware, ducts, filters and maintenance clearances occupy real space; they are not details to squeeze into the remaining gap.
A simple heat-loss worksheet
The following figures are invented solely to demonstrate the arithmetic. They are not product data, a CWS design or a cooling-unit selection. The real schedule must use the selected manufacturers’ information and the applicable design method.
| Item | Quantity | Assumed loss each | Subtotal |
|---|---|---|---|
| Drive A | 1 | 420 W | 420 W |
| Drive B | 1 | 420 W | 420 W |
| Drive C | 1 | 220 W | 220 W |
| Control power and electronics | 1 group | 70 W | 70 W |
| Other assessed internal losses | 1 group | 90 W | 90 W |
| Total for this illustrative scenario | All listed items | 420 + 420 + 220 + 70 + 90 | 1,220 W |
Record the drive model, operating load and source of each loss figure alongside the worksheet so the assumptions can be checked during design review.
Sum of assumed internal losses, before selecting the thermal solution.
The total is an input, not a verified cooling capacity. It does not establish component temperatures, local hot spots, airflow distribution or the thermal behaviour of the complete assembly. The enclosure, external conditions and verification method still have to be considered.
If one drive is normally on standby, document the applicable operating scenarios and its standby losses. Do not delete it from the calculation without confirming whether both drives can operate during testing, changeover or another required mode.
Compare three heat-removal routes
Use the enclosure surface
Assess whether the construction and temperature difference can reject the required heat while keeping components within their permitted conditions. The available external surface and installation position matter.
Use ambient-air ventilation
Consider this where the surrounding air and contamination conditions permit it. Fans and filters require suitable air paths and maintenance; ambient air cannot cool the interior below its own temperature.
Keep the air circuits separate
Select an air-to-air heat exchanger, refrigeration cooling unit or air-to-water arrangement for the actual conditions. These methods have different temperature and infrastructure requirements; separate air paths alone do not establish cooling capacity.
An air-to-air heat exchanger still needs a suitable temperature difference to transfer heat to the surrounding air; it cannot refrigerate the enclosure below ambient. A refrigeration unit or suitable water circuit can address different conditions, subject to its rated performance. Rittal distinguishes these approaches by environment and required output. Check condensate handling, maintenance and heat rejection as well as capacity.
Coordinate the solution with the enclosure’s ingress protection and materials. Adding a vent, fan, cut-out or cooler changes the construction and needs to be included in the assessment.
Draw the air path and the service path
Show where cool air enters, how it reaches equipment inlets and where heated air leaves. Follow drive-manufacturer clearances and mounting instructions. Avoid assuming that a low average cabinet temperature proves every device receives adequate cooling.
Check whether the proposed arrangement can recirculate hot discharge into another drive inlet. Consider barriers, ducts, adjacent cabinets and nearby room air outlets. Confirm access to filters, fans, cooling units and the drive itself without disturbing unrelated circuits unnecessarily.
Cable routing belongs in the same drawing. Motor cables, screening connections, control wiring and any required reactors or filters can change space and thermal conditions. Keep EMC and installation instructions with the selected drive package.
Close the loop with the switchroom designer
A cabinet cooler does not make heat disappear. Identify where its condenser or other rejection path releases energy. If the heat is discharged into the switchroom, the room-services designer needs that load and the relevant cooling-equipment input power, along with other room loads.
Agree the room design conditions with the enclosure designer. Include the consequences of a cooling fault, the alarms required, and the approved equipment response. The plant’s operating needs determine the response; a universal trip or automatic restart rule is not appropriate.
For outdoor equipment, include the actual exposure and the manufacturer’s treatment of solar loading and weather. For humid or intermittently operated spaces, consider condensation and the operating conditions during shutdown as well as full production.
Where CWS supplies a prefabricated switchroom, resolve the drive enclosure and room-services interfaces within the agreed package.
Keep the thermal design traceable
Retain the loss schedule, equipment references, operating assumptions, ambient conditions, layout and cooling selection with the assembly documentation. A changed drive, higher duty or later feeder addition can invalidate an earlier assumption.
Agree the temperature-rise verification basis appropriate to the assembly and specified edition. A generic heat-loss sum, a photograph of a fan or a brief no-load factory run is not equivalent to demonstrating the loaded assembly’s thermal performance.