33 Clyde Street, Invercargill 9810, NZ
Mon-Fri 08:00 AM - 05:00 PM
Post Image
06 Apr, 2026
Posted by Chris Wilson
0 comment

What Fault Rating Does a Switchboard Need?

Switchboard Specification
March 2026 · 7 min read

A switchboard needs a fault rating that matches the actual fault conditions at its point of installation. This is not something that should be guessed, copied from a previous job, or treated as a generic default. This guide explains what fault rating means in practice, why it matters, and what information should be confirmed before pricing or manufacture begins.


Switchboard Fault Rating Guide — Clive Wilson Switchboards NZ
Fault rating is a core technical requirement that affects safety, equipment suitability, protection strategy, switchboard construction, device selection, quotation accuracy and compliance. If the required fault level is unclear at the enquiry stage, the board may be priced on assumptions. If those assumptions later change, the design and commercial basis can change with them.

What Is Switchboard Fault Rating NZ?

In practical project terms, fault rating refers to the prospective short-circuit current (PSCC) that the switchboard assembly and its associated protective devices must be capable of withstanding or interrupting under fault conditions.
This figure is determined by the electrical system upstream of the board, including the supply network, transformer impedance and the distribution hierarchy. It is not selected by the switchboard manufacturer. It is a characteristic of the system at the point of installation, and it must be provided as a design input.
The switchboard must then be specified and built so that every component in the assembly is rated to safely withstand or interrupt that level of fault current. This includes the busbars, incoming device, outgoing protective devices and the enclosure assembly itself.

Key point: Fault rating is a design input that comes from the electrical system. It is not a choice made by the switchboard builder, and it should not be assumed or carried over from a different project without verification.

Why Fault Rating Matters

A switchboard may appear physically suitable for a project and still be wrong if the fault rating basis has not been correctly established.

Equipment suitability

Every component in the switchboard, including the incomer, outgoing circuit breakers, busbars and isolators, must have an interrupting or withstand rating that meets or exceeds the prospective fault current at the installation point. If any device in the assembly is underrated for the fault level present, it may fail to operate safely under fault conditions.

Protection and coordination

Fault rating sits alongside the broader protection philosophy for the project. Understanding the fault level at each board in the system is part of ensuring that protective devices are correctly selected and coordinated so that only the device closest to a fault operates, leaving the rest of the system unaffected.

Cost and construction

Higher fault duties can influence switchgear selection, the busbar system specification, internal construction detail and overall quotation value. These are not minor variations. An incorrect fault rating assumption can require significant redesign if corrected late in the project.

Compliance under AS/NZS 61439

New Zealand’s mandatory standard for low-voltage switchgear and controlgear assemblies requires that the assembly be verified as suitable for the electrical conditions of the installation. The fault level at the point of supply is a fundamental input to that verification. A board that has not been assessed against the correct fault level cannot be reliably demonstrated as compliant.

What Determines the Fault Rating a Switchboard Needs?

The required fault rating is determined by the characteristics of the electrical system at the point where the board will be connected. The main factors include:

  • The upstream supply network and its available fault current
  • Transformer impedance and rating, where a transformer feeds the board
  • The impedance of cables and conductors between the source and the board
  • The board’s position in the distribution hierarchy
  • Any contribution from on-site generation or large motor loads
Quick estimate for transformer-fed boards: If you know the transformer kVA rating, secondary voltage, and nameplate impedance, our free NZ Transformer Fault Current Calculator provides a conservative prospective fault current estimate at the LV terminals — useful as a starting point before a full fault study is available.

From a manufacturer and quotation perspective, the fault level should be provided by the project’s electrical designer or confirmed from documented network information. It is not something the switchboard manufacturer can calculate from the project description alone.

Why the Location of the Board Matters

Not every board on a site requires the same fault rating. The available fault current decreases with distance from the source due to the impedance of the cables and conductors in the path. A main switchboard connected close to the incoming supply will typically face a higher prospective fault current than a distribution board fed from it downstream.
This is one reason a main switchboard and a sub-distribution board may need to be assessed separately, even on the same project. The closer the board is to the source, the more critical it becomes to correctly establish the fault level at that point in the system.

Fault Rating vs Breaker Rating

A common source of confusion is the assumption that the interrupting rating of the circuit breaker alone answers the whole question. It does not.
The interrupting capacity of a protective device is the maximum fault current that device can safely break. But the switchboard fault rating covers the entire assembly, including busbars, connections, enclosure construction and all other components, not just the protective devices.
In practice:

  • The breaker rating must be equal to or greater than the prospective fault current at that point
  • The busbar and assembly must also be rated to withstand the thermal and mechanical stresses of the fault current for the duration of the fault clearance time
  • The complete assembly design and protection philosophy must be aligned

Treating a single device rating as the whole answer can result in an undersized or non-compliant assembly.

How Fault Rating Affects the Quotation

Fault rating has direct commercial implications. Depending on the project it can affect device selection, busbar construction, internal assembly design, enclosure arrangement, compliance documentation and overall cost.
That is why fault rating should be treated as a core enquiry input alongside main rating, outgoing schedule, board role in the system, segregation requirements and enclosure IP requirements. If any of these are missing, the quotation is more likely to rely on assumptions that may need to be resolved later.

Common Mistakes That Cause Problems

  • Fault level not stated in the enquiry. If the required fault duty is not identified, the board will be priced on a default assumption that may later prove incorrect
  • Using a previous project as the basis. Even if two jobs appear similar, the fault conditions at each point of installation may be different
  • Treating breaker rating as the complete answer. The protective device rating is one part of a broader assembly and system assessment
  • Raising fault duty requirements too late. Changes after the quote is prepared can trigger redesign, repricing and programme delay
  • Assuming the same fault level applies to all boards on a site. Downstream boards typically face a lower fault level due to cable impedance, but this should be confirmed rather than assumed

Before Requesting a Switchboard Quote

  • Has the prospective fault current at the point of installation been confirmed?
  • Is the board’s role and position in the distribution hierarchy clear?
  • Are the main rating and incomer details known?
  • Is the outgoing feeder schedule available?
  • Are segregation and enclosure requirements defined?
  • Is the quote based on a stated fault rating rather than an assumed default?
  • Has the consultant specification or standards requirement been provided?

Final Thoughts

The correct fault rating for a switchboard is not a generic choice. It should reflect the actual prospective short-circuit current at the point of installation and be confirmed clearly in the project documentation before pricing or manufacture proceeds.
Where the fault level is uncertain, clarifying it early supports safer design decisions, clearer equipment selection, more accurate quotations and fewer avoidable revisions later in the project.
Once a board is built and installed, the confirmed fault rating should be clearly and permanently identified on the assembly. For engraved fault rating labels and circuit identification plates, see Clive Wilson’s engraving service.

Related Articles

Need help confirming fault rating for your switchboard project?

Clive Wilson Switchboards · 31–33 Clyde Street, Invercargill · 03 218 3459

Request a Quote

Call Us

Contact Us