Logstrup switchboards / Clive Wilson

Logstrup capability.
Built by CWS in NZ.

Modular low-voltage switchboards manufactured in Invercargill using the Logstrup platform. Platform capability extends to 8,000 A, with the usable rating established for the project’s assembly and operating conditions.

CWS Logstrup switchboard installed on site
Modular construction

Configure the lineup around the project

The Logstrup system provides a modular framework for LV switchboard construction. CWS assembles and wires the equipment in Invercargill, coordinating the enclosure, busbar system, switching devices and outgoing circuits with the project specification.

Applications include main switchboards and motor control centres. The appropriate arrangement depends on the incoming supply, load mix, separation requirements and maintenance strategy.

Logstrup modular switchboard framework
Project-specific ratings

8,000 A describes platform capability

A platform maximum is not a rating for every completed board. Current capacity, temperature rise, fault withstand, enclosure protection and the selected devices need to be considered together for the proposed assembly.

Supply the prospective fault level and required withstand duration, along with operating voltage, ambient conditions and installation constraints. Verification information must apply to the actual design and its permitted variations.

Access and maintenance

Fixed, removable or withdrawable arrangements can be considered where supported by the selected system and equipment. Discuss safe access, separation, cable termination space and replacement strategy during design.

From specification to factory test

Agree the evidence and deliverables

Logstrup enquiry requirements
RequirementWhat to include
Supply and loadsSingle-line diagram, circuit schedule and normal or alternative supply arrangements.
RatingsAssembly current, fault requirements, environment and applicable specification.
ConstructionAccess, separation, device arrangement, cable entry and spare capacity.
DeliveryRoom dimensions, transport sections, lifting and installation sequence.
RecordsApproved drawings, verification documentation and factory-test requirements.

See main switchboard design considerations and our NZ switchboard standards guide for related specification questions.

Start a conversation

Discuss a Logstrup assembly

Send your single-line diagram and specification to CWS. We will review the modular arrangement and identify the information needed to establish the project ratings.

Printable quote checklist (PDF)Email your checklist, drawings and schedules to estimating@clivewilson.co.nz. Leave unknown items blank.