Fixed, demountable or withdrawable MCC: which suits your plant?

Compare fixed, demountable and withdrawable MCCs by connections, replacement work, spares and outage needs, using Simotrol and Logstrup examples.

Chris Wilson, Clive Wilson SwitchboardsPublished 4 min read
FixedDemountableWithdrawable
Choose the MCC arrangement around the replacement task and the outage your plant can accept. Fixed feeders use installed connections; demountable units can be removed using the system’s connection arrangement; withdrawable units have defined connected, test or isolated positions where the system provides them. Compare the actual power and control connections before specifying the mechanism.

Three arrangements, three maintenance questions

Fixed

Equipment is mounted and connected in a fixed arrangement. Ask which conductors, fixings and adjacent parts must be accessed to replace the component or feeder.

Demountable

A functional unit can be removed using the system’s intended arrangement. Ask exactly which power and auxiliary connections disconnect, and which require separate work.

Withdrawable

A unit has defined operating or isolation positions within a designed withdrawal system. Ask which positions exist, what remains connected and how the unit is secured.

Terminology is not identical across every manufacturer. “Plug-in”, “removable” and “demountable” should be backed by a drawing and the relevant operating instructions. A label alone does not tell the maintenance team how the incoming, outgoing and control connections are arranged.

For example, Logstrup’s published withdrawable-unit information describes dedicated positions and outgoing terminals in a cable section. That is a characteristic of the specified system, not a promise that any MCC module offers the same arrangement.

Compare the task, not the label

Questions to resolve for each proposed configuration
DecisionFixedDemountableWithdrawable
Replacement workDisconnect and replace the installed component or feeder within the planned isolation.Remove the functional unit; plug-in and manually disconnected connections depend on the system.Move to the specified isolated position and exchange the unit using the manufacturer’s procedure. Check which connections remain fixed.
SparesPlan component references and any preassembled replacements.Match spare units to the actual module and connections.Match spare units, coding, ratings and control configuration.
Operating accessCheck doors, barriers and terminal access.Check module handling and access to fixed connections.Allow movement, handling space and secure storage.
ControlsRecord wiring and settings needed after replacement.Identify plugs, terminals, software and parameter transfer.Define test-position behaviour and control-power arrangements.
InvestmentUsually the simplest construction. Assess the labour and outage needed for replacement.Additional modular interfaces can reduce replacement work; price the actual arrangement and spares.Withdrawal mechanisms, test facilities and handling space add scope. Compare their value against plant availability requirements.

Fixed construction often suits planned shutdowns. Demountable or withdrawable arrangements can reduce replacement work where the plant has compatible units, documented settings and a clear maintenance procedure. Compare whole-of-life cost and outage needs, not the mechanism alone.

Three questions that change the specification

These questions belong in the first design discussion. Discovering them after the cubicle widths and cable sections are fixed can affect the complete layout.

Separation and withdrawability are separate decisions

Forms of internal separation describe how specified parts of the assembly are separated. They do not, on their own, describe the feeder’s withdrawal mechanism, establish internal-arc performance or authorise work with exposed live parts.

Specify the form, access requirements and functional-unit arrangement separately. Then check that the proposed combination is supported by the assembly system and its verification evidence. The forms of separation guide explains that part of the brief.

Start with the CWS platform that fits

Simotrol is CWS’ primary industrial MSB and MCC platform, with demountable units in supported configurations. CWS also builds Logstrup fixed and withdrawable arrangements. Send the motor schedule, fault duty and maintenance requirements so we can propose the construction for the job.

Do not transfer a rating or feature from one platform brochure to a different construction. Ask which evidence covers the proposed arrangement, including any non-standard unit, equipment substitution or future extension.

A short decision record to keep with the specification

  1. List the critical motor duties and the acceptable loss of service.
  2. Describe the actual component or feeder replacement task.
  3. Confirm the proposed power, control and communication connections.
  4. Specify the isolation and access requirements without assuming live work.
  5. Agree the spare-unit strategy, handling and post-replacement checks.
  6. Record the selected platform, configuration, evidence and accepted limitations.

Send that record with the motor schedule and we will propose a Simotrol or Logstrup arrangement with the connections, ratings and maintenance approach identified.

Logstrup MCC elevation drawing, shown for illustration
Logstrup MCC elevation drawing, shown for illustration.

References and further reading